Parameter Range 0 - Start delay 0-60m (5s)1 - Preheat
0-60s (0s)2 - Crank attempt 3-60s (10s)3 - Crank rest 3-60s  (10s)4 - Safety delay 8-60s  (8s)5 - Warming up 0-60s
(0s)6 - Return delay 0-60m  (30s)7 - Cooling run 0-60m  (60s)8 - E.T.S. hold 0-60s  (0s)9 - Sensor fail 1-5s (2s)10 - Fail to Stop 10-60s  (60s)
11 - Low Oil Press.5-150PSI (15PSI)12 - High Temp 90-150°C  (95°C)
13 - Under Speed 0-3600RPM (1250RPM)14 - Over Speed 300-5000RPM  (1750RPM)15 – Under freq’0-60Hz (40Hz)16  - Over freq’
50-72Hz (57Hz)17 - Charge Alt Failure 0-25V (8V DC)18 - Flywheel teeth 46-300 (0)
19 - CT Primary
10-6000A (500A)
Parameter
Selections 20 - Alternator poles
0,2,4
,6,821 - Oil pressure input
0 - Not used
1 - Digital, close for low pressure
2 - Digital, open for low pressure
3 - VDO 0-5bar
4 - VDO 0-10bar
5 - Datcon 5bar
6 - Datcon 10bar
7 - Datcon 7bar
8 - Murphy 7bar
9 - User configured
22 - Coolant temp input
0 - Not used
1 - Digital, close for high temperature
2 - Digital, open for high temperature
3 - VDO 40°C to 120°C
4 - Datcon High
5 - Datcon Low
6 - Murphy
7 - Cummins
8 - PT100
9 - User configured
ACCESSING THE CONFIGURATION EDITOR Press the Stop/Reset  and Info
buttons
simultaneously.
• The LED beside the AUTO button will
flash continuously to indicate that
configuration mode has been entered.• The first configuration
setting is displayed:
From the configuration table, this example is displaying Start Delay  (parameter 0). It is currently set to 5 seconds .
(Factory default settings are shown in the configuration table in bold italic  text)EDITING A PARAMETER
• Enter the editor as described above.
• Press  + / -  to scroll through the parameters to
the one you want to change.• Press 9 to enter edit
mode. The  symbol will flash on the display to indicate that edit mode has been entered.• Press + / - to change the parameter to the
desired value.• Press 9 to save the value and exit edit mode for
this parameter.
• The  symbol will be removed from the display
to indicate that edit mode has been exited.
• To select another value to edit, press the + / -buttons. Continuing to press the + and – buttons will cycle through the adjustable parameters as shown in the following lists.
D E E P  S E A  E L E C T R O N I C S
Model 5110 Configuration and installation instructions
051-178ISSUE 2
button. Ensure you have saved any changes  button first
DIMENSIONS
240mm x 172mm x 57mm (9.5” x 6.8” x 2.25”)
PANEL CUTOUT 220mm x 160mm (8.7” x 6.3”)
Parameter Selections
23 - Fast loading0 - No
enabled  1 - Yes
24 - AC system0 - 3 phases 4 wires
1 - 1 phase
2 wire
2 -
3 phases 3 wires
3 - 2 phases 3 wires 25 - Oil pressure0 - Bar/PSI
display units  1 - kPa
Parameter Selection
26 - Output 10 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18 - Maintenance due
27 - Output 20 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18 - Maintenance due Parameter Selection
28 - Output 30 - Unused
1 - Preheat mode 0
editor bar2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18-Maintenance due
29 - LCD 10 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18 - Maintenance due
30 - LCD 20 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18M i t d
Parameter Selection
31 - LCD 30 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18 - Maintenance due
32 - LCD 40 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Close Generator
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
18 - Maintenance due
Parameter Selection
33 - Input 10 - Delayed, Warning, close to activate
1 - Delayed, Warning, open to activate
2 - Immediate, Warning, close to activate
3 - Immediate, Warning, open to activate
4 - Delayed, Shutdown, close to activate
5 - Delayed, Shutdown, open to activate
6 -Immediate, Shutdown, close to activate
7 - Immediate, Shutdown, open to activate
8 - Remote Start, close to activate
9 - Remote Start, open to activate
34 - Input 20 - Delayed, Warning, close to activate
1 - Delayed, Warning, open to activate
2 - Immediate, Warning, close to activate
3 - Immediate, Warning, open to activate
4 - Delayed, Shutdown, close to activate
5 - Delayed, Shutdown, open to activate
6 - Immediate, Shutdown, close to activate
7 - Immediate, Shutdown, open to activate
8 - Electrical trip, close to activate
9 - Electrical trip, open to activate
35 - Input 30 - Delayed, Warning, close to activate
1 - Delayed, Warning, open to activate
2 - Immediate, Warning, close to activate
3 - Immediate, Warning, open to activate
4 - Delayed, Shutdown, close to activate
5 - Delayed, Shutdown, open to activate
6 - Immediate, Shutdown, close to activat e
7 - Immediate, Shutdown, open to activate
8 - Lamp test, close to activate
9 - Lamp test, open to activate
36 - Input 40 - Delayed, Warning, close to activate
1 - Delayed, Warning, open to activate
2 - Immediate, Warning, close to activate
3 - Immediate, Warning, open to activate
4 - Delayed, Shutdown, close to activate
5 - Delayed, Shutdown, open to activate
6 - Immediate, Shutdown, close to activat e
7 - Immediate, Shutdown, open to activate
37 - Input 50 - Delayed, Warning, close to activate
1 - Delayed, Warning, open to activate
2 - Immediate, Warning, close to activate
3 - Immediate, Warning, open to activate
4 - Delayed, Shutdown, close to activate
5 - Delayed, Shutdown, open to activate
6 - Immediate, Shutdown, close to activate
7 - Immediate, Shutdown, open to activate
8 - Oil pressure, Shutdown, close to activate
9 - Oil pressure, Shutdown, open to activate